Mold Found Below a Leaking Mini-Split

A commercial client in Waco, Texas requested a limited mold assessment after an employee raised concern about possible mold in a work area. The assessment focused on two rooms. In the Front Room, a wall-mounted mini-split was actively dripping, with evidence of water traveling down the wall to the floor line. Surface testing confirmed fungal growth behind the flexible cove base below the mini-split. Air samples from both rooms were below the outdoor reference and did not indicate airborne fungal amplification at the sampled locations and time.

Waco, Texas · Commercial manufacturing facility · Commercial Properties

  • mini split
  • ductless ac
  • condensate leak
  • commercial mold
  • cove base
  • wall mold
  • aspergillus penicillium
  • alternaria
  • stachybotrys
  • ulocladium
  • air sampling
  • surface sampling
  • hvac moisture
View Case Study →
Mold growth exposed behind detached wall trim after commercial plumbing leak

Mold Found After a Repaired Plumbing Leak in a Grand Prairie Commercial Building

A commercial building owner requested an independent assessment after a plumbing leak in a tenant-occupied veterinary facility had been repaired. The wall had reportedly remained open for several weeks to dry. Staff reported intermittent floor saturation over approximately two years, stopping after the repair. No active water or significant comparative moisture anomaly was observed at inspection, and accessible closet surfaces showed no visible mold. In Exam Room 1, previously detached trim exposed stained drywall that tested Heavy for Chaetomium, Aspergillus/Penicillium-like structures and hyphal fragments. A sample from the shared wall cavity supported concern that fungal growth may also be present within the concealed assembly; its extent and conditions beneath the flooring were not determined.

Grand Prairie, Texas · Commercial veterinary facility · Commercial Properties

  • commercial mold
  • plumbing leak
  • hidden mold
  • wall cavity
  • chaetomium
  • aspergillus penicillium
  • stachybotrys
  • water damage
  • baseboard
  • veterinary facility
  • grand prairie
  • floor moisture
View Case Study →